Modbus devices with limited requests

Maximum query size and delay between queries

Written By Evolo Support

Last updated About 19 hours ago

Why can't I read data from my Modbus device?

Some Modbus slaves can only handle a limited number of registers per request. If Evolo optimizes and accesses an invalid register range, the entire query will fail.

How can I fix this?

  • Reduce the maximum query size: Set the maximum to 1 or 2 (depending on 16-bit/32-bit). This prevents the query from including invalid registers.

  • Increase the delay between queries: This gives the slave more time to respond.

Example of an error situation:

  • Valid registers: 1, 2, 3, 4

  • Invalid registers: 5, 6, 7

  • Evolo It might try “address 1, count 7,” fail due to 5–7, and also throw an error for 1–4.

The error appears in the system log as:

evolo-gateway [error] 2025-05-20 14:10:44: Modbus exception 2: Illegal data address… slave: 1, register: 0, count: 78

Where can I find the settings?

  • Go to Configuration → Interface and open the device interface.

    • Max query size: listed in the form. The number of records Evolo queries in a single request, maximum 125.

    • Delay between queries: Open Advanced Settings. Specified in milliseconds, from 0 to 10,000.

Where can I find information about the maximum query size?
See the Modbus device manual or contact the manufacturer/supplier.