Skip to main content
Energy Setup

Set up nodes and floats

Add the nodes to the energy group and connect them using floats—that is, the meters between the nodes.

Written By Evolo Support

Last updated 1 day ago

Before You Begin

A flow with a physical meter only supports accumulating data points for energy. This means that the data point must increase over time, such as a meter reading. Voltage and power cannot be used as meter readings. The data point must have the Accumulating log type.

Types of Nodes and Flows

A node is a location where energy flows in or out. You can choose from several node types:

  • Grid Inlet
    : The point where energy is bought and sold to the grid.

  • Generation
    : Solar panels or other local energy generation.

  • Distribution
    : The point from which energy is distributed further, such as a distribution panel or a heating plant.

  • Heat Pump
    : Displayed as a distribution node in the node tree and flow diagram. Heat from the surroundings comes from an Ambient Energy node (Generation, Thermal Heat) with a flow from the Residual Meter into the heat pump. A heat pump that alternates between heating and cooling is a single node with two outgoing flows: to Heat Production (Thermal Heat) and to Cooling Production, where you select Thermal Cooling as the medium.

  • Chiller
    Also appears as a distribution. It does not require an ambient energy node, and the control does not alert you when it is providing more cooling than it is consuming electricity.

  • Consumer
    : End-use consumption, such as ventilation, lighting, a tenant, or a single course.

  • Battery
    : Energy storage. Use import and export on the flow for charging and discharging.

A flow is the meter between two nodes. You can choose from several meter types:

  • Physical Meter
    Reads cumulative energy data from a data point in Evolo.

  • Elhub meter
    : Retrieves data directly from Elhub; see Add Elhub meters to Evolo (Add Elhub Meters in Evolo).

  • Residual
    Meter: Has no data point. Evolo calculates the value based on the other flows around the node. Used for unmetered consumption during a distribution, and for the energy a heat pump extracts from the environment.

How to Set Up Nodes and Flows

First, add the nodes, and then connect them to flows. The example covers a physical meter:

1

Open Energy Monitoring

Go to Setup and select Energy Tracking. There must be at least one energy group.

Select the energy group in Select Energy Group.

2

Add nodes

Click Add Node at the top of the page.

Select Node Type and enter the name of the node. Below the name field, you’ll see suggestions for common names, such as Main Distribution or Ventilation. Enter a description if desired.

Select the Medium for the node: Electricity, Thermal Heating, Thermal Cooling, Domestic Hot Water, or Other.

Under “Other Settings,” you can specify an icon, color, order, number of square meters (for consumption per m²), and label. Click “Create,” and repeat for each node.

3

Add a flow

Once the energy group has at least two nodes, click Add Flow.

Enter a name for the flow. Optionally, enter a description.

Select From node (the node the energy comes from) and To node (the node the energy goes to).

4

Select meter type

Select Meter Type; in this example, physical meter. The meter type cannot be changed after the flow has been created.

5

Select data points

Select Data Point for energy in the direction of the arrow (import).

If applicable, select Data Point for Energy Against Arrow Direction (export) if energy can flow in both directions—for example, to the grid when the building sells electricity.

If applicable, select Data Point for Power in the direction of the arrow. You can then select Power in the Consumption tab. Click Create.

The configuration page with the controls, the "Nodes and Meters" table, and the energy flow preview
Set up nodes and floats

Below the Nodes and Meters table, the setup is displayed as a flowchart, so you can verify that the nodes are connected as intended.

At the top of the page, Evolo checks the setup. You’ll receive a notification if something results in incorrect numbers—for example, if the same data point is used on two flows, if a flow is missing a data point, or if a distribution point is supplying more than it’s receiving. An electric boiler that is measured only by an electricity meter can use the same data point for the incoming and outgoing flows, since incoming electricity equals outgoing heat.

If you’re setting up a new energy group, you can use the Wizard. It asks for grid intake, distributions, consumers, and generation, and creates the nodes and flows for you.

With the Reuse Setup feature, you can export the nodes and flows to Excel and import them into an empty energy group.

Main Meter and Submeters

The hierarchy is derived from the flows. The flow from a grid connection to a distribution point is the main meter, and the flows continuing from the distribution point are submeters. This is also how the nodes are displayed in the node tree in the energy monitoring system.

Nodes under the same node are displayed in the order specified in the Order field, with the lowest number first. You can also move a node using Move Up and Move Down in the menu on the row in the Nodes and Meters table. The order applies to the table, the node tree, and the flow diagram.

Each node calculates its own input minus its output:

  • A distribution automatically sums the flows into it.

  • Any flow not measured further from a distribution is displayed as unmeasured consumption. If you want this to be a separate node in the node tree, add a flow with “Residual Meter.”

A flow can also go from a distribution point for one tenant to a node for another tenant. In that case, the energy is subtracted from the first tenant’s total and added to the second tenant’s total.