Set up data point forwarding
The application is used to pass values between data points, including between different automation protocols.
Written By Evolo Support
Last updated 2 days ago
Here's how to do it
Open the app list
Go to Settings and select Apps. Click Add App.
Enter a name and select a gateway
Enter a name, a description if desired, and select a gateway.
Add data point pairs
Add the data point pairs to be forwarded. Select the data point to read from and the data point to write to. Click Create.
Fields
Gateway: the gateway on which the application will run. This cannot be changed after the application has been created.
Name: The name of the application. If this field is left blank, the application will be named “Forward Data Point.”
Description: Optional description.
Type: Select “Forward Data Point.” This field becomes available once you’ve selected a gateway.
Enabled: is on by default. Uncheck this box to stop the application on the gateway without deleting the configuration.
Read Data Point (the From Data Point column): the data point from which the value is retrieved.
Write Data Point (To Data Point column): the data point to which the value is forwarded.
All data points must be located on the same gateway, and each data point can only be used once in the application.
When the value is forwarded
The value is forwarded when it changes, and otherwise every 5 minutes. How quickly a change is received depends on the protocol. For Modbus, this is controlled by the polling interval on the interface.
If the read point does not respond, nothing is forwarded for Modbus, BACnet, and OPC UA. For KNX, MQTT, and Loxone, the last known value is forwarded every 5 minutes.
For example, you can forward a Modbus data point to a BACnet data point. When the gateway receives data at the read point, the value is forwarded to the write point.