Compare energy consumption using degree-day adjustment

Degree-day adjustment makes it easier to compare energy consumption between periods with different weather conditions. In Evolo, this is used to compare energy performance over time and across buildings in a more equitable manner.

Written By Evolo Support

Last updated 1 day ago

What is a degree-day?

A degree-day indicates how much the outdoor temperature deviates from a building’s set point over time. The set point is the temperature at which the building normally does not require heating or cooling to maintain the desired indoor temperature. In Norway, 17 °C is often used as the baseline.

Example: If the outdoor temperature is 10 °C and the balance point is 17 °C, that results in 7 heating degrees for that day.

Why use degree-day correction?

Energy consumption is affected by the weather. A cold month will often result in higher consumption than a mild month, even if the building is used in the same way.

How does it work?

Degree-day correction adjusts only the portion of consumption that goes toward heating—that is, the portion that increases as it gets colder. The rest—such as lighting, ventilation, equipment, and cooling—remains as measured.

Evolo first calculates how much extra energy the building uses per degree-day, based on the node’s own measurements of energy and outdoor temperature. Then, each period is adjusted from the degree-days it actually had to the degree-days you’re correcting to:

Adjusted consumption = measured consumption + kWh per degree-day × (degree-days adjusted to − actual degree-days)

Example: A node used 10,000 kWh in a month with 300 degree days, and the building uses an extra 10 kWh per degree day. If the month is adjusted to 250 degree days, the consumption becomes 10,000 + 10 × (250 − 300) = 9,500 kWh. A cold month is adjusted downward, and a mild month is adjusted upward.

How degree-day correction works in Evolo

In the energy monitoring for a building, select “Correction” under Temperature Correction in the left-hand panel.

The selection appears on the Comparison tab, in the Period-to-Period view.
When comparing energy consumption across multiple buildings, check the box for Temperature Correction.

You can choose:

  • Uncorrected: displays consumption as it was measured.

  • Temperature-corrected: Each period is adjusted to the average weather conditions for the same period in the years you’re reviewing. Use this when you want to see if consumption has increased or decreased from year to year, without a cold or mild year skewing the results.

  • Normal-Year-Adjusted: Each period is adjusted to a normal year for the building’s location. The normal year is the average weather for 1991–2020 from the nearest weather station operated by the Norwegian Meteorological Institute, and the station is listed in the drop-down menu. Use this when you want to compare with other buildings or key figures, or track the building over a long period against a fixed reference.

The "Correction" field, with "Uncorrected," "Temperature-Corrected," and "Normal-Year-Corrected"
Temperature Correction

For each day of the year, Evolo retrieves the normal daily mean temperature from the weather station. The degree days for the day are calculated as 17 °C minus the normal temperature, but never below zero. The degree days are totaled by month.

Example: ALTA AIRPORT has 738 degree days in a typical January, 102 in July, and 5,362 in a typical year. With a resolution of one week or one day, the month’s degree-days are distributed evenly across the days, so a day in January in Alta receives about 24 degree-days.

The balance point is 17 °C for all nodes.

For individual nodes

The correction requires at least 12 full periods with both energy data and outdoor temperature, and that consumption actually follows the outdoor temperature. Otherwise, the figures are displayed uncorrected, with an explanation. Nodes with “Medium Tap Water” or “Thermal Cooling” are not corrected and are displayed as measured.

When comparing buildings

Each node is converted to the average weather conditions for the selected nodes in each period.

If temperature data is missing

If temperature data is missing for a period, or if the period is not yet complete, it is displayed as measured. Without an outdoor temperature reading for the building, you can only select “Uncorrected.” “Normal-Year Corrected” requires that the building be connected to a weather station.